35 | Nortec SAM-e Installation
Nortec Electrode Steam-Line
Table 1: Electrode Steam-Line
Nortec
Humidifier
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss per
foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
RH Duct 120V 5 3/4" 7/8” 0.06 8 ft
RH Duct 240V 10 3/4" 7/8” 0.06 15 ft
EL 005 5 3/4" 7/8” 0.06 7 ft
EL 010 10 3/4" 7/8” 0.06 12 ft
EL 020 20 3/4" 7/8” 0.06 17 ft
EL 030 30 3/4" 7/8” 0.06 22 ft
EL 050 50 1-1/2” 1-3/4" 0.11 43 ft
EL 075 75 1-1/2” 1-3/4" 0.11 47 ft
EL 100 100 1-1/2” 1-3/4" 0.11 47 ft
EL 150 (2 outlets) 150 2 x 1-1/2” 1-3/4" 0.11 47 ft
EL 200 (2 outlets) 200 2 x 1-1/2” 1-3/4" 0.11 50 ft
Based on 3” duct static pressure.
Maximum duct static pressure for electrode steam units is 6” w.c.
A fill cup extension kit can be used on EL to overcome higher duct static pressure, or for
longer steam line runs. (Consult factory).