Nortec SAM-e Installation | 56
Troubleshooting
Steam tubes discharge water:
1 Steam supply pipe is not insulated.
2 Steam supply pipe not properly drained or sloped.
3 Manifold or adapter condensate drain is clogged or malfunctioning.
4 Excessive back-pressure in condensate drain pipe (due to pressure in secondary condensate
drain); must be piped to non-pressurized condensate return.
5 Primary and secondary condensate drains are both joined together.
6 Condensate line has been routed too high (causing static back pressure).
Maintenance
Inspect Nortec SAM-e at start-up.
1 For humidifier maintenance schedule, refer to Installation, Operation, and Maintenance
Manual for your humidifier.
Spare Parts
SAM-e coupling seal for steam tubes (1 per tube)
Insertion stop (1 per tube) (Galvanized)
Insertion stop (1 per tube) (Stainless Steel)
5/16” Locknuts, bolts, washers (Galvanized)
5/16” Locknuts, bolts, washers (Stainless Steel)
1/4" bolts, washers (1 per tube) (Galvanized)
1/4" bolts, washers (1 per tube) (Stainless Steel)
SAM-e insulated tube strapping
SAM-e insulated header strapping
SAM-e insulated dual-inlet header strap (for second inlet)