14. Troubleshooting
Problem Possible cause Remedy
Permanent acoustic signal • Heavy operation of the • Remove valve opera-
and display of "F1" on the valve or blocked valve. ting mechanism.
valve operating mechanism's • Manually check
display. valve operation.
•Re-install valve ope-
rating mechanism.
•If necessary ask a
heating expert for
advice.
Permanent acoustic signal • Control range too wide. • Re-install valve
and display of "F2" on the • Valve operating mechanism operating mecha-
valve operating mechanism's not mounted on heating nism.
display. valve. • Unsuitable valve.
• Put a 1mm spacer
(e.g. a shim) between
heating valve and
actuator.
Permanent acoustic signal • Control range too narrow. • Re-install valve
and display of "F3" on the operating mecha-
valve operating mechanism's nism.
display. • Unsuitable valve.
No antenna symbol displayed • Radio connection failure • Install heating control
on the valve operating due to interference. in a different loca-
mechanism's display. At an • Heating control battery tion.
interval of one hour the valve empty. • Replace heating
operating mechanism generates • Wrong heating control control batteries.
a sequence of tones. The valve code. • Transmit the current
opening is 30%. safety code to the
valve operating
mechanism.
"Low Bat" symbol displayed on • Valve operating mecha- • Replace the batteries.
the display, for one hour and at nism batteries almost
an interval of 2 minutes the valve empty.
operating mechanism generates
a sequence of tones.
Display of "LOC" when key is • Key lock is active. • Deactivate the key
pressed. lock.
96
3. Explications des symboles
Le symbole de l´éclair dans un triangle est utilisé pour signaler
un danger pour votre santé, p. ex. par un choc électrique.
Dans ce mode d’emploi, un point d’exclamation placé dans un
triangle signale les informations importantes à respecter
impérativement.
☞
Le symbole de la « main »précède les recommandations et indi-
cations d´utilisation particulières.
105