EMA90 - USER MANUAL
-52-
Load Power, indicates the rated powers expressed in kW of the all loads.
The Load 1 corresponds to digital output 1 (Do1) and so on…
Priority On, indicates the connection priority of each load. The load with
8 priority will be the first to be connected, while the load with 1 priority will
be the last. The 0 priority indicates load always disconnected while the 9
priority means that the load is always connected. The default value is 0.
Priority Off, indicates the disconnection of each load. The load with 1
priority will be the first to be disconnected, while the load with 8 priority
will be the last. The 9 priority indicates load always connected while the 0
priority means that the load is always disconnected. The default value is
9.
Delay On, indicates the minimum time, expressed in seconds, for which
the load must be connected (ON) before being disconnected. Range
0÷3600 seconds.
Delay Off, indicates the minimum time, expressed in seconds, for which
the load must be disconnected (OFF) before being connected. Range
0÷3600 seconds.