Accelnet & Stepnet Plus Panels STO Manual 16-01338 Rev 00
Page 16 of 34 Copley Controls
7.2 STO Function Specifications
When STO is active, motor current that can cause rotation (or motion in
the case of a linear motor) is not applied by either Axis A or Axis B. The
PWM outputs of both axes are disabled and cannot source or sink current.
This STO function is defined in IEC-61800-5-2, clause 4.2.2.2
IEC-61508-1, IEC-61508-2, IEC-61800-5-2, ISO 13489-1
Category & Performance Level
Category 3, Performance Level PL d
Hardware only – Type A components
TÜV SÜD Functional Safety Mark (Pending)
Signals (Functional Safety Related)
STO-IN1(+), STO-IN1(-), STO-IN2(+), STO-IN2(-), Frame ground (shield)
+24 Vdc, typical, maximum withstand voltage +60 Vdc
SELV power supply required
STO Input Energize Voltage
Vin-HI ≥ +15.0 Vdc between STO-IN(+) and STO-IN(-)
STO Input De-energize Voltage
Vin-LO ≤ +6.0 Vdc or open between STO-IN(+) and STO-IN(-)
STO-IN1: 11.2 mA, STO-IN2: 11.2 mA
Current flow is into STO-IN1(+) and STO-IN2(+) and out of STO-IN1(-) and
STO-IN2(-). STO inputs must be connected in parallel.
From Vin ≤ 6.0 Vdc or open to PWM outputs disabled (off): 2 ms
Opto-isolators, +24 VDC compatible
7.3 Environmental Specifications
0 °C to 45 °C per IEC 60068-2-1:2007 and IEC 60068-2:2007
0 to 95 %RH, non-condensing per IEC 60068-2-78:2001
-40 °C to 85 °C per IEC 60068-2-1:2007 and IEC 60068-2-2:2007
≤ 2000 m per IEC 60068-2-13:1983
Pollution Degree 2 per IEC 60664-1:2007
10
g
, 10 ms, 1/2 Sine Pulse per IEC 60068-2-27:2008
2
g
, peak, 10~500 Hz (Sine) per IEC 60068-2-6:2007