3-1-2. ON / OFF/ REMOTE (Main) switch:
a. Before installing the inverter, make sure the main switch
must
be “OFF”.
b. Before using the remote unit, make sure the main switch
must be “ REMOTE”.
3-1-3. Input Level:Display Input Voltages
LED Status DC 12V DC 24V DC 48V
RED Blink (slow) 10.5~10.9 21.0~21.8 42.0~43.6
RED 10.9~11.3 21.8~22.6 43.6~45.2
ORANGE 11.3~12.0 22.6~24.0 45.2~48.0
GREEN 12.0~14.0 24.0~28.0 48.0~56.0
ORANGE Blink 14.0~14.7 28.0~29.4 56.0~58.8
OVER RED BLINK 14.7 29.4 58.8