Also, use only high quality copper wire and keep cable length short, a
maximum of 3 - 6 feet.
WARNING!
Make sure all the DC connections are
tight (torque to 9 – 10 ft-lbs, 11.7 – 13
Nm). Loose connections could result
overheat in a potential hazard.
WARNING!
The installation of a fuse must be on
positive cable.
Failure to place a fuse on “+” cables
running between the inverter and battery
may cause damage to the inverter and
will void warranty.