CR240 USER MANUAL
14/17
Cotes dehumidifier: 650000
Manual number: 140772
Revision: B
COTES.COM
6 / SERVICE AND MAINTENANCE
6.1 HOW TO SERVICE THIS DEHUMIDIFIER
Safety instructions
WARNING
Before opening the dehumidifier, make sure that the electric power
is switched off on the main switch (or pull the plug!).
Before opening the dehumidifier, make sure the power is turned off at the mains before you open any cover of
the dehumidifier. Otherwise, there will be a risk of electric shock. Also be aware that the heater element may be
hot if the lid is removed right after the dehumidifier is turned off.
Service and maintenance work on this dehumidifier
Cotes designs its dehumidifier units so that they are as robust as possible, and only need a minimum of service
and maintenance. None of the components require lubrication or adjustment.
The only maintenance work you need to do is listed below.
Service area must be clear at all times. Diagrams and manual must be kept near the machine.
Machine will automatically start-up in case of power loss and recover of electricity.
Service and maintenance in wind turbine installation
Only three things should be done during normal operation and following the normal service intervals
for installation in the nacelle / tower of a wind turbine.:
Replace air filters.
Check the rotation of the rotor.
Check the power consumption of the electric heater (reading 4,5A on the Ammeter, during operation).
If the rotor rotates during operation, and the energy consumption of the complete machine shows app. 4,5A,
you can be almost sure that the dehumidifier is operating at an optimum.
We nevertheless recommend some periodic verification of the entire dehumidifier, to see if all internal functions
are OK and checking of cables to be well fixed, and for damage of the insulation.