Room Pressure Monitor and Controller - User Guide © 2012 CRITICAL ROOM CONTROL 13
Network Setup
Network: BACnet
Baud Rate:
MAC Address:
Instance ID:
Debug Info:
Save Changes Exit -No Change
38400
25
33321
Show Don’t Show
MAC Address: 0 – 254
Note: MAC address must be unique for each device
on a specific MS/TP trunk
Instance ID: 1 – 4,194,304
Note: Instance ID must be unique for
each device on the overall network
Debug Info: Displays Network information
on main screen to assist in debugging
network related issues
u
ss:
Note: MA
address mus
on a s
ific MS/TP trun
Select network Baud Rate: 9600, 19200,
38400, 57600, 76800 or 115,200