Room Pressure Monitor and Controller - User Guide © 2012 CRITICAL ROOM CONTROLϭϱ
9.2 ŶĞƚWŽŝŶƚDĂƉ:
ANALOG VALUES
General
AV 0 Analog Input 1 Ňoat Read Only
(0-100%)
AV 1 Analog Input 2 Ňoat Read Only (0-100%)
AV 2 Analog Input 3 Ňoat Read Only (0-100%)
AV 3 Analog Input 4 Ňoat Read Only (0-100%)
Primary Room
AV 4 Current P * Float Read trite
Inches of water column Pascals
AV 5 P Status * Int Read trite 0= normal, 1 = loss of pressure, 2= alarm
AV 6 Iso Set Point * Ňoat Read trite Inches of water column Pascals
AV 7 Non - Iso Set Point * Ňoat Read trite Inches of water column Pascals
AV 8 Sensor ,igh Ňoat Read Only Inches of water column Pascals
AV 9 Sensor Low Ňoat Read Only Inches of water column Pascals
AV 10 Alarm ,igh Ňoat Read Only Inches of water column Pascals
AV 11 Alarm Low Ňoat Read Only Inches of water column Pascals
AV 48 Pressure Oīset Ňoat Read Only
Secondary Room
AV 12 Current P * Float Read trite
Inches of water column
Pascals
AV 13 P Status * Int Read trite 0= normal, 1 = loss of pressure, 2= alarm
AV 14 Iso Set Point * Ňoat Read trite Inches of water column Pascals
AV 15 Non - Iso Set Point * Ňoat Read trite Inches of water column Pascals
AV 16 Sensor ,igh Ňoat Read Only Inches of water column Pascals
AV 17 Sensor Low Ňoat Read Only Inches of water column Pascals
AV 18 Alarm ,igh Ňoat Read Only Inches of water column Pascals
AV 19 Alarm Low Ňoat Read Only Inches of water column Pascals
AV 49 Pressure Oīset Ňoat Read Only
Room General
AV 20 Current Mode Int Read trite
1= Iso, 2= clearing, ϱ= cleaning, 3 = non iso, 4 = ǀacant
AV 21 isplay Units Int Read Only 1 = "tC, 2 = PA
AV 22 Clearing Time int Read Only Minutes
AV 23 Clearing Time LeŌ int Read Only Seconds
More Info - Primary
AV 24 Point 1 Current Value * Float Read trite
AV 25 Point 2 Current Value * Float Read trite
AV 26 Point 3 Current Value * Float Read
trite
AV 27 Point 4 Current Value * Float Read trite
AV 28 Point 1 Set Point * Float Read trite
AV 29 Point 2 Set Point * Float Read trite
AV 30 Point 3 Set Point * Float Read trite
AV 31 Point 4 Set Point * Float Read trite
AV 32 Point 1 Alarm Status * Int Read
trite 0=Not used (Grey), 1= OK (green), 2= Audible ALARM
(red), 3= Muted Alarm (red with white strip)
AV 33 Point 2 Alarm Status * Int Read trite 0=Not used (Grey), 1= OK (green), 2= Audible ALARM
(red), 3= Muted Alarm (red with white strip)
AV 34 Point 3 Alarm Status * Int Read trite 0=Not used (Grey), 1= OK (green), 2= Audible ALARM
(red), 3= Muted Alarm (red with white strip)
AV 35 Point 4 Alarm Status * Int Read trite 0=Not used (Grey), 1= OK (green), 2= Audible ALARM
(red), 3= Muted Alarm (red with white strip)