Note: If you are using the door contact feature: When the door is open the audible alarm delay
ǁŝůůďĞĂĐƟǀĞ/ĨƚŚĞĚŽŽƌŝƐĐůŽƐĞĚƚŚĞĂƵĚŝďůĞĂůĂƌŵĚĞůĂLJǁŝůůďĞŝŶĂĐƟǀĞĂŶĚĂŶĂƵĚŝďůĞĂůĂƌŵ
ǁŝůůƐŽƵŶĚŝŵŵĞĚŝĂƚĞůLJǁŚĞŶĞǀĞƌƉƌĞƐƐƵƌĞŝƐůŽƐƚ
ALARM TRIGGER:
Local: Uses alarm high / low below as an alarm range
Network: Pressure Alarm triggered via BACnet Point
ROOM NAME: Text used for the
room icon on the Main Screen
et
oo
PRESSURE INPUT: Signal from the Pressure
Sensor
• Network
• AI 0-5v, 0-10v
• AI 1-5v, 2-10v
• AI 4-20mA
• Not Used (will hide Room Pressure Icon on
front screen and disable alarm parameters)
Pressure Sensor High /
Pressure Sensor Low:
High and low range of the
pressure sensor / transducer
ISO Set Point: Value that the RPC1 or RPC2 use to
control pressure when in ISO and Clearing Mode (via
PID loop). Also used by Alarm High / Low to calculate
pressure alarm.
ALARM HIGH / LOW: Pressure alarm range. These
values are relative to "ISO Set Point" – so that the
actual value of alarm high will be ISO Set Point +
Alarm High, and Alarm Low will be ISO Set Point –
Alarm Low
: Pressure alarm ran
e. These
v
l
r
r
l
tiv
t
ISO Set Poin
–
th
t th
actual value of alarm hi
h will be
Alarm High
nd Alarm Low will be
SO Set Point –
Alarm Lo
ALARM DELAY: The number of seconds of delay before the
audible pressure alarm will sound. "Off" will turn off the audible
pressure alarm.
ACK TIME OUT time in seconds for alarm
to resound after initial acknowledgment is
made and alarm condition has not reset.
OFFSET (Pressure): Adds to or subtracts
from the room's pressure readout.
ZERO (Pressure): Automatically enters a value
for OFFSET by calculating current pressure
readout as zero or no pressure.
NO ISO SET POINT: Value that the RPC1 and
RPC2 use to control pressure when in Vacant,
Non ISO, and Cleaning Mode (via PID loop).