I-Tech HD DriveCore Series Power Ampliers
Operation Manual
page 39
7.7.13 Amplifier Settings  
The Amplifier Output Enable button turns each channel on 
or off.
Error Reporting
The I-Tech amplifier can detect four different error conditions 
per channel and errors in the AC line voltage. Each error type 
can be indi vidually configured to report the error through the 
network. Network reported errors appear in the control software 
Event Log. The following describes each error source.
Clip: A clip detector is provided each channel. These monitors 
will indicate any clip condition (> 0.05% distortion) in the 
amplifier channel. The clip detectors also can indicate Thermal 
Level Control limiting. 
The I-Tech HD can be configured to report if an excessive 
number of output clip events occur in either amplifier channel. 
The clip events are considered an error if they exceed the 
defined count per the defined unit of time. 
The Count Control sets the maximum number of events before 
the error is reported. The range is 1 to 100. The Time Control 
defines the amount of time that the events are counted before 
starting the counting process over. Its range is 1 to 10 seconds. 
Note: Clip events are defined as the start of each clip and every 
10 milliseconds the amplifier is in clip thereafter. Using a high 
count set ting with a short time setting may result in clip errors 
never being detected.
Thermal: Errors can be generated for excessive temperature 
in the output section of the amplifier channel. The Threshold 
Control sets the level that, if exceeded, will generate the error 
report. This control has a range of 1 to 100%.
Line voltage: The AC line voltage can be monitored and an 
error generated whenever the voltage is outside of the limits set 
by the soft ware. 
Fan: Using the ON button, you can enable reports of any fan 
errors.
Continuous Load Monitoring
The load supervision feature allows real-time monitoring of the 
load connected to each amplifier channel. When enabled, the I-
Tech contin uously monitors the amplifier output voltage and 
current, and calcu lates the long-term average load impedance. 
The measured load impedance is compared against the user-
defined high and low limits. If either limit is exceeded, the 
status indicator and, if enabled, the System Architect Error 
Reporting functions alert the user of the problem. There are six 
controls and two indicators for each channel:
On: Enables or disables the load-supervision function.
Load Status: This indicator shows the present sta tus of the 
load impedance with respect to the user-defined high and low 
limits.
Average Impedance: Shows the average impedance for the 
connected load. 
High Limit: Sets the upper bound above which the system 
will report a “high” error status.
Low Limit: Sets the lower bound below which the system will 
report a “low” error status.
Nominal Impedance: Sets the expected average impedance 
for the connected load. This value determines the output signal 
level required for the test. This parameter is also used by the 
average power limiter to determine the expected power 
threshold. You set this field to the nominal impedance of the 
connected load per channel. 
Report Errors via Network: When this is turned on, high 
and low load errors are sent via the network to System Architect 
software.
7 Advanced Operation