EasyManua.ls Logo

Cubic COM5000-8 - Page 28

Default Icon
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
351804-1 Rev. 100
COM5000-8 TECHNICAL MANUAL
18
In addition to the System Controller and PA module LED display, the T-4180 Status display will show
operational parameters and specific fault conditions.
The first of two T-4180 status screens is evoked as follows:
From the T-4180 default screen press [NEXT]
On the new screen press [PASTAT]
The first of two status screen appears
T-4180 Status screen #1:
Press [MORE] to view the second status screen.
T-4180 Status screen #2:
The fault indications are as follows:
a. On screen #1, if a fault is detected, "OK" will change to "FLT".
b. "COMS" show status of serial communication with the PA module. If communication with a PA
module is lost, “OK” will change to “FLT”.
c. "FLTS" show PA module faults in HEX format. The definition is shown below.
o A critical fault requires the 50V supply voltage to be turned OFF and then ON to reset the
fault.
o Most other faults are reset by un-keying and then re-keying the Transmitter.
FREQ: 29.999 000 MHZ Antenna Intlock OK
FWD POWER = 0000 WATTS Cabinet Intlock OK
REV POWER = 000 WATTS Combiner Temp OK
Combiner Fan OK
SWR of 0.0:1
MORE
RETURN
FLTS P1 P2 P3 P4
000 000 000 000
COMS P1 P2 P3 P4
OK OK OK OK
MORE
RETURN