EasyManua.ls Logo

Cuenod GX107 - User Manual

Cuenod GX107
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
10/2007 - Art. Nr. 13 017 700B
NC12, NC16, NC21 GX107/8
NC12, NC16, NC21 GX207/8
Инструкция по эксплуатациии
газовых горелок............................... 39-56
Operating instructions
Gas burners ......................................... 3-20
Betriebsanleitung
Gasbrenner ........................................ 21-38
Библиотека СОК

Table of Contents

Questions and Answers

  • U
    ucampbellAug 11, 2025
    What to do if there is no flame at the end of safety time in Cuenod GX107 Burner?
    • J
      jennifer29Aug 11, 2025
      If there's no flame at the end of the safety time for your Cuenod Burner, you should first check the fuel-oil level in the tank and ensure that all valves are open. If equipped, check and reset the pressure. Then, inspect the pump operation, pressure, coupling, filter, and electric valve. Next, examine the ignition circuit, electrodes, and electrode settings, cleaning the electrodes as necessary. If the issue persists, consider replacing the electrodes, ignition cables, transformer, or nozzle.
  • L
    Larry OsborneAug 19, 2025
    What to do if Cuenod GX107 runs briefly then stops and emits a signal?
    • C
      Christopher ElliottAug 19, 2025
      If your Cuenod Burner starts briefly, stops, and signals that it was in a set pattern of 9, the control unit may have stopped intentionally or there might be a loss of flame. Try resetting the control unit first. If that doesn't work, clean or replace the flame monitor, reset combustion, and if necessary, replace the control unit.
  • H
    hannah67Aug 26, 2025
    Why Cuenod Burner fails to start after thermostatic shutdown but the control unit gives no fault signal?
    • J
      Jennifer JohnsonAug 26, 2025
      If your Cuenod Burner fails to start after a thermostatic shutdown and the control unit shows no fault signal, it could be due to a decrease or absence of supply voltage. Check the origin of this voltage issue. Alternatively, the control unit itself might be defective and need replacement.
  • K
    Kristine ScottSep 3, 2025
    How to fix parasitic flame during preventilation in Cuenod GX107 Burner?
    • L
      lgutierrezSep 3, 2025
      If you observe a parasitic flame during preventilation or pre-ignition time in your Cuenod Burner, clean or replace the electric valve, or the pump if it has an integral electric valve.

Cuenod GX107 Specifications

General IconGeneral
BrandCuenod
ModelGX107
CategoryBurner
LanguageEnglish

Related product manuals