2. Normal Defrost Mode
FUNCTIONS ( Defrost Mode )
HEATER
DEFROTING
PAUSE
FAN DELAY
1) HEATER DEFROSTING
- Defrost heater is switch on until Defrost Sensor temperature reaches 13C.
- Heater operation time
; 30 seconds - Heater is ON free of Defrost Sensor.
; 30 minutes - When Defrost Sensor is malfunction. ( D1 error )
; 60 minutes - Heater maximum operation time. ( F3 error)
2) PAUSE
- After Defrost Heater switch OFF, Compressor dosen't run within 10 minutes.
3) FAN DELAY
- Freezer & Refrigerator fan switch on after 5miunuts' cmopressor running.
Normal Mode
PAUSE
OFF
Division
Compressor
Freezer Fan OFF
ON
Refrigerator Fan
OFF
HEATER DEFROST
OFF
OFF
ONDefrsot Heater OFFOFF
OFF
FAN DELAY
OFF
5min
OFF
10min
30min ( D1 error )
60min ( F3 error)
Time