Installation and operation manual
6
FWEC3
Advanced plus electr
onic controller
FC66002765
DIGIT
AL 1 OUTPUT
P09
P10 = 0 (NO CONTACT) P10 = 1 (NC CONTACT)
OPEN
CONTACT
CLOSED
CONTACT
OPEN
CONTACT
CLOSED
CONTACT
0
NOT USED -- -- -- --
1
OPERATING MODE SUMMER WINTER WINTER SUMMER
2
UNIT IN COOLING OR
HEATING MODE
NO YES YES NO
3
UNIT IN COOLING MODE NO YES YES NO
4
UNIT IN HEATING MODE NO YES YES NO
5
CONTROLLER STATUS OFF ON ON OFF
6
ALARM TRIGGERED NO YES YES NO
7
EXTERNAL
DEHUMIDIFICATION CALL
NO YES YES NO
8
EXTERNAL
HUMIDIFICATION CALL
NO YES YES NO
9
HIGH ROOM
TEMPERATURE
NO YES YES NO
10
LOW ROOM
TEMPERATURE
NO YES YES NO
11
NOT USED -- -- -- --
12
LOW WATER
TEMPERATURE
YES NO NO YES
DIGIT
AL 2 OUTPUT
P11
P12 = 0 (NO CONT
ACT) P12 = 1 (NC CONTACT)
OPEN
CONTACT
CLOSED
CONTACT
OPEN
CONTACT
CLOSED
CONTACT
0
-- -- -- --
1
OPERATING MODE SUMMER WINTER WINTER SUMMER
2
UNIT IN COOLING OR
HEATING MODE
NO YES YES NO
3
UNIT IN COOLING MODE NO YES YES NO
4
UNIT IN HEATING MODE NO YES YES NO
5
CONTROLLER STATUS OFF ON ON OFF
6
ALARM TRIGGERED NO YES YES NO
7
EXTERNAL
DEHUMIDIFICATION CALL
NO YES YES NO
8
EXTERNAL
HUMIDIFICATION CALL
NO YES YES NO
9
HIGH ROOM
TEMPERATURE
NO YES YES NO
10
LOW ROOM
TEMPERATURE
NO YES YES NO
11
WATER CIRCUIT
ENABLED FOR COOLING
YES NO NO YES
12
WATER CIRCUIT
ENABLED FOR HEATING
YES NO NO YES
CONFIGURATION OF DIGITAL OUTPUTS
(PARAMETERS P09,P10,P11,P12)
P09,P11
= 8
The contact is used to switch ON/OFF any exter
nal device
for humidifying the air (heating mode only). The ON/OFF
logic is based on a reading of the humidity in the room and
the SETPOINT selected with parameter P13. It follows the
diagram shown:
P09,P11
= 9
The status of the contact indicates whether the air tempe-
ratur
e is too high compared to the temperature SETPOINT
(only in the “summer” mode); the ON/OFF logic is thus tied
to the value of the temperature SETPOINT, according to the
following step:
P09,P11
= 10
The status of the contact indicates whether the air temperatur
e
is too low compared to the temperature SETPOINT (only in the
“winter” mode); the ON/OFF logic is thus tied to the value of
the temperature SETPOINT, according to the following step:
P09,P11
= 11
The digital output is not gover
ned by the controller; the contact
is always open.
P09,P11
= 12
The contact status indicates that water temperatur
e is low.
The activation/deactivation logic follows the step:
The two tables below provide a detailed explanation of the
meaning of the contact associated with each digital output:
Air humidity
Air temperatur
e
Air temperatur
e
W
ater temperature