30 AGZ 025D through 190D OMM 1166-1
Transitions between these states are shown in the following diagram.
OFF
RUNPUMPDOWN
T3
T2
T4
T
1
POWER
ON
T
5
PREOPEN
T6
T1 Off to Preopen
No compressors are running and any compressor on circuit is commanded to start (see unit capacity
control)
T2 Preopen to Run
5 seconds has passed
T3 Run to Pumpdown
Any of the following are required:
Last compressor on circuit is commanded to stop
Unit State = Pumpdown
Circuit switch is open
Circuit mode is disable
Circuit Pumpdown alarm is active
T4 Pumpdown to Off
Any of the following are required:
Evaporator Pressure < Pumpdown Pressure Value
Unit State = Off
Circuit Rapid Stop alarm is active
T5 Run to Off
Any of the following are required:
Unit State = Off
Circuit Rapid Stop alarm is active
A low ambient start attempt failed
T6 Preopen to Off
Any of the following are required:
Unit State = Off
Unit State = Pumpdown
Circuit switch is open
Circuit mode is disable
Circuit Rapid Stop alarm is active
Circuit Pumpdown alarm is active