24 AGZ 025D through 190D OMM 1166-1
Enum
Status
Conditions
6
Off:Keypad Disable
Unit State = Off and Unit Enable Set Point = Disable
7
Off:Remote Switch
Unit State = Off and Remote Switch is open
8
Off:BAS Disable
Unit State = Off, Control Source = Network, and BAS Enable =
false
9
Off:Unit Switch
Unit State = Off and Unit Switch = Disable
10
Off:Test Mode
Unit State = Off and Unit Mode = Test
11
Auto:Wait for load
Unit State = Auto, no circuits running, and LWT is less than the
active set point + startup delta
12
Auto:Evap Recirc
Unit State = Auto and Evaporator State = Start
13
Auto:Wait for flow
Unit State = Auto, Evaporator State = Start, and Flow Switch is
open
14
Auto:Pumpdown
Unit State = Pumpdown
15
Auto:Max Pulldown
Unit State = Auto, max pulldown rate has been met or exceeded
16
Auto:Unit Cap Limit
Unit State = Auto, unit capacity limit has been met or exceeded
17
Auto: High Ambient Limit
---
18
Config Changed, Reboot
Required
A configuration change requiring a reboot has occurred but
controller has not been rebooted yet.
Evaporator Pump Control
For control of the evaporator pumps, three evaporator pump control states should be used:
Off - No pump on.
Start Pump is on, water loop is being recirculated.
Run Pump is on, water loop has been recirculated and circuits can start if needed.
Transitions between these states are shown in the following diagram.
OFF
STARTRUN
T
3
T2
T
4
T
1
POWER
ON
T5
T1 Off to Start
Requires any of the following
Unit state = Auto
LWT is less than the Evap Freeze set point 0.6°C (1.1°F) and LWT sensor fault isn’t active
T2 Start to Run
Requires the following
Flow ok for time longer than evaporator recirculate time set point

Table of Contents