24 AGZ 025D through 190D OMM 1166-1
Unit State = Off and Unit Enable Set Point = Disable
Unit State = Off and Remote Switch is open
Unit State = Off, Control Source = Network, and BAS Enable =
false
Unit State = Off and Unit Switch = Disable
Unit State = Off and Unit Mode = Test
Unit State = Auto, no circuits running, and LWT is less than the
active set point + startup delta
Unit State = Auto and Evaporator State = Start
Unit State = Auto, Evaporator State = Start, and Flow Switch is
open
Unit State = Auto, max pulldown rate has been met or exceeded
Unit State = Auto, unit capacity limit has been met or exceeded
Config Changed, Reboot
Required
A configuration change requiring a reboot has occurred but
controller has not been rebooted yet.
Evaporator Pump Control
For control of the evaporator pumps, three evaporator pump control states should be used:
Off - No pump on.
Start – Pump is on, water loop is being recirculated.
Run – Pump is on, water loop has been recirculated and circuits can start if needed.
Transitions between these states are shown in the following diagram.
OFF
STARTRUN
T
3
T2
T
4
T
1
POWER
ON
T5
T1 – Off to Start
Requires any of the following
Unit state = Auto
LWT is less than the Evap Freeze set point – 0.6°C (1.1°F) and LWT sensor fault isn’t active
T2 – Start to Run
Requires the following
Flow ok for time longer than evaporator recirculate time set point