5 Electrical installation
Installation manual
11
EPRA14~18DAV3+W1
Daikin Altherma 3 H HT
4P586100-1B – 2019.09
Use the factory-mounted cable.
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
L N PE
b
a
L
N
Q1DI
1N~,
50 Hz,
230 V AC
F1B
1
3
2
4
II
BRN
BLU
YLW/GRN
b
a
L
N
a Factory-mounted power supply cable
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2
pole, 32A fuse, C curve.
Q1DI Earth leakage circuit breaker (30mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
Route the cable through the frame.
Connect the wires to the terminal block (make sure the
numbers match with the numbers on the indoor unit) and the
earth screw.
Fix the cable with a cable tie.
Wires: (3+GND)×1.5mm²
1 2 3
1
2
3
3 (Optional) Drain tube heater cable:
Make sure the heating element of the drain tube heater is
completely inside the drain tube.
Route the cable through the frame.
Connect the wires to the terminal block and the earth screw.
Fix the cable with cable ties.
Wires: (2+GND)×0.75mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115W (0.5A)