5 Electrical installation
Installation manual
13
EPRA14~18DAV3+W1
Daikin Altherma 3 H HT
4P586100-1B – 2019.09
1 2 3
1
2
3
3 (Optional) Drain tube heater cable:
Make sure the heating element of the drain tube heater is
completely inside the drain tube.
Route the cable through the frame.
Connect the wires to the terminal block and the earth screw.
Fix the cable with cable ties.
Wires: (2+GND)×0.75mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115W (0.5A)
1 2
5.4 To reposition the air thermistor on
the outdoor unit
This procedure is only necessary in areas with low ambient
temperatures.
Required accessory (delivered with the unit):
Thermistor fixture.
1
2 3
Click
4 5
6
7