5 Electrical installation
Installation manual
13
ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P586453-1B – 2020.01
Model (power
supply)
Connections to backup heater power
supply
*6V (6V: 1N~230V)
1N~, 50 Hz
230 V AC
SWB
4
3
6
5
2
1
K5M
14
13
Q1DI
1
2
3
4
5
6
7
8
F1B
II I I
NL
X6M
BRN
GRY
BLU1
BLU2
*6V (6T1: 3~230V)
SWB
3~, 50 Hz
230 V AC
4
3
6
5
2
1
K5M
14
13
1
2
3
4
5
6
7
8
F1B
II I I
Q1DI
L1 L2 L3
X6M
BRN
GRY
BLU1
BLU2
*9W (3N~400V)
3N~, 50 Hz
400 V AC
SWB
Q1DI
L1 L2 L3 N
1
2
3
4
5
6
7
8
F1B
II I I
X6M
2
1
K5M
4
3
6
5
14
13
BRN
GRY
BLK
BLU
F1B Overcurrent fuse (field supply). Recommended fuse:
4‑pole; 20A; curve 400V; tripping class C.
K5M Safety contactor (in the switch box)
Q1DI Earth leakage circuit breaker (field supply)
SWB Switch box
X6M Terminal (field supply)
NOTICE
Do NOT cut or remove the backup heater power supply
cable.
5.3.3 To connect the shut-off valve
INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
Wires: 2×0.75mm²
Maximum running current: 100mA
230VAC supplied by PCB
[2.D] Shut off valve
1 Open the following (see "3.2.1To open the indoor unit"[45]):
1 Front panel
2 Switch box cover
3 Switch box
2 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
NO
NC
C
5 6
X2M
C
21 28
X2M
C
5 6
X2M
C
21 29
X2M
B
X2M