6 Electrical installation
Installation manual
32
EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECHO
4P663483-1A – 2021.11
INFORMATION
ALWAYS configure the safety thermostat after it is
installed. Without configuration, the unit will ignore the
safety thermostat contact.
6.3.13 To connect a Smart Grid
This topic describes 2 possible ways to connect the indoor unit to a
Smart Grid:
In case of low voltage Smart Grid contacts
In case of high voltage Smart Grid contacts. This requires the
installation of the Smart Grid relay kit (EKRELSG).
The 2 incoming Smart Grid contacts can activate the following Smart
Grid modes:
Smart Grid contact Smart Grid operation mode
1
2
0 0 Free running
0 1 Forced off
1 0 Recommended on
1 1 Forced on
The use of a Smart Grid pulse meter is not mandatory:
If Smart Grid pulse meter is… Then [9.8.8] Limit setting kW
is…
Used
([9.A.2] Electricity meter 2
None)
Not applicable
Not used
([9.A.2] Electricity meter 2 =
None)
Applicable
In case of low voltage Smart Grid contacts
Wires (Smart Grid pulse meter): 0.5mm²
Wires (low voltage Smart Grid contacts): 0.5mm²
[9.8.4]=3 (Benefit kWh power supply = Smart grid)
[9.8.5] Smart grid operation mode
[9.8.6] Allow electrical heaters
[9.8.7] Enable room buffering
[9.8.8] Limit setting kW
The wiring of the Smart Grid in case of low voltage contacts is as
follows:
8
7
S11S
65
S S10
43
X 5M1
S S4
109
a
21
a Jumper (factory-mounted). If you also connect a safety
thermostat (Q4L), replace the jumper with the safety
thermostat wires.
S4S Smart Grid pulse meter
1
/S10S
Low voltage Smart Grid contact 1
2
/S11S
Low voltage Smart Grid contact 2
1 Connect the wiring as follows:
B
A
B
X 5 M1
A
X 5M.41
X 5M.31
S4S
X 5M.101
X 5M.91
S10S
X 5M.61
X 5M.51
S11S
2
1
3 4 5 6 9 107 8
2 Fix the cables with cable ties to the cable tie mountings.
In case of high voltage Smart Grid contacts
Wires (Smart Grid pulse meter): 0.5mm²
Wires (high voltage Smart Grid contacts): 1mm²
[9.8.4]=3 (Benefit kWh power supply = Smart grid)
[9.8.5] Smart grid operation mode
[9.8.6] Allow electrical heaters
[9.8.7] Enable room buffering
[9.8.8] Limit setting kW
The wiring of the Smart Grid in case of high voltage contacts is as
follows:
S4S
910
X 5M1X 5M1
78
K2AK1A
5634
K1ALNL
N
STEP 3
a b c d e f
STEP 1 STEP 2
A1
A2
25242523X1 M2
K2A
A1
A2
2 1
STEP 1 Smart Grid relay kit installation
STEP 2 Low voltage connections
STEP 3 High voltage connections
1
High voltage Smart Grid contact 1
2
High voltage Smart Grid contact 2
a, b Coil sides of relays
c, d Contact sides of relays
e Jumper (factory-mounted). If you also connect a safety
thermostat (Q4L), replace the jumper with the safety
thermostat wires.
f Smart Grid pulse meter
1 Install the switch box metal insert.