4.1.3 Installation patterns
Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type Allowed patterns
Living room, kitchen, garage, attic, basement, storage room 1, 2, 3
Technical room (i.e. room that is NEVER occupied by persons) 1, 2, 3, 4
PATTERN 1 PATTERN 2 PATTERN 3 PATTERN 4
H
release
H
release
2a
b
c2
c1
A
B
2b
Ventilation openings N/A Between room A and B N/A Between room A and
outside
Minimum floor area Room A Room A + Room B N/A N/A
Chimney Might be needed Might be needed Connected to outside N/A
Release in case of
refrigerant leakage
Inside room A Inside room A Outside Inside room A
Restrictions See "PATTERN 1"[411], "PATTERN 2"[411], "PATTERN 3"[413], and
"Tables for PATTERN 1, 2 and 3"[413]
See "PATTERN 4"[415]
Room A (= room where indoor unit is installed)
Room B (= adjacent room)
a If no chimney is installed, this is the default point of release
in case of refrigerant leakage.
If needed, you can connect a chimney here:
▪ Unit's connection point for the chimney = 1" male thread.
Use a compatible counterpart for the chimney.
▪ Make sure the connection is airtight.
b Chimney
c1 Bottom opening for natural ventilation
c2 Top opening for natural ventilation
H
release
Actual release height:
: Without chimney. From floor to top of the unit.
▪ For 300l units => H
release
=1.89m
▪ For 500l units => H
release
=1.90m
: With chimney. From floor to top of the chimney.
▪ For 300l units => H
release
=1.89m + Chimney height
▪ For 500l units => H
release
=1.90m + Chimney height
Installation with chimney connected to the outside. The
release height is not relevant. There are no requirements to
the minimum floor area.
N/A Not applicable
Minimum floor area / Release height:
▪ The minimum floor area requirements depend on the release
height of the refrigerant in case of a leakage. The higher the
release height, the lower the minimum floor area requirements.
▪ The default point of release (without chimney) is at the top of the
unit. To decrease the minimum floor area requirements, you can
increase the release height by installing a chimney. If the chimney
leads outside of the building, there are no requirements anymore
to the minimum floor area.
▪ You can also take advantage of the floor area of the adjacent
room (= room B) by providing ventilation openings between the
two rooms.
▪ For installations in technical rooms (i.e. room that is NEVER
occupied by persons), additionally to patterns 1, 2 and 3, you can
also use PATTERN4. For this pattern there are no requirements
to the minimum floor area if you provide 2 openings (one at the
bottom, one at the top) between the room and the outside to
ensure natural ventilation. The room must be protected from frost.
When connecting a chimney
▪ Install the chimney socket (delivered as accessory) to the plate
heat exchanger box.