EasyManua.ls Logo

Daikin Altherma EABH16DA6V - Setting up the Domestic Hot Water Tank; System Layout - Standalone DHW Tank; Selecting the Volume and Desired Temperature for the DHW Tank

Daikin Altherma EABH16DA6V
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Application guidelines
Installer reference guide
16
EPGA11~16DAV3 + EABH/X16DA6V+9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10
The auxiliary contact can be:
An outdoor temperature thermostat
An electricity tariff contact
A manually operated contact
Setup: Connect the following field wiring:
L
N
H
Com
A
K2AK1A
X2M
B
TI
K2AK1A
Indoor/Auto/Boiler
3530 X Y
Indoor
B
TI
Boiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional)
K1A Auxiliary relay for activation of indoor unit (field supply)
K2A Auxiliary relay for activation of boiler (field supply)
Indoor Indoor unit
Auto Automatic
Boiler Boiler
NOTICE
Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between
indoor unit and auxiliary boiler.
If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that
it is NOT influenced or turned ON/OFF by direct
sunlight.
Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.
Setpoint of the auxiliary gas boiler
To prevent freeze-up of the water piping, the auxiliary gas boiler
must have a fixed setpoint ≥55°C, or a weather-dependent setpoint
≥T
min
.
0
–30 –25 –20 –15 –10 –5 0 5
20
30
40
50
60
10
T
a
(°C)
T
min
(°C)
T
a
Outdoor temperature
T
min
Minimum weather-dependent setpoint for auxiliary gas
boiler
5.4 Setting up the domestic hot water
tank
5.4.1 System layout – Standalone DHW tank
FHL1
FHL2
FHL3
M
a c hf g
f
i j
d
b
e
a Outdoor unit
b Indoor unit
c Heat exchanger
d Backup heater
e Pump
f Shut-off valve
g Motorised 3‑way valve
h Collector (field supply)
i DHW tank
j Heat exchanger coil
FHL1...3 Underfloor heating
5.4.2 Selecting the volume and desired
temperature for the DHW tank
People experience water as hot when its temperature is 40°C.
Therefore, the DHW consumption is always expressed as equivalent
hot water volume at 40°C. However, you can set the DHW tank
temperature at a higher temperature (example: 53°C), which is then
mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank
consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the volume and desired temperature for the DHW
tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption
(equivalent hot water volume at 40°C) using typical water volumes:
Question Typical water volume
How many showers are needed
per day?
1shower = 10min×10l/min =
100l
How many baths are needed per
day?
1bath = 150l
How much water is needed at the
kitchen sink per day?
1sink = 2min×5l/min = 10l
Are there any other domestic hot
water needs?
Example: If the DHW consumption of a family (4 persons) per day
is as follows:
3 showers
1 bath
3 sink volumes

Table of Contents

Other manuals for Daikin Altherma EABH16DA6V

Related product manuals