14 | Disposal
Installer reference guide
221
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
a
c
b
d
d
e
a Gas stop valve
b Closing direction
c Hexagonal wrench
d Valve cap
e Liquid stop valve
14.3 To start and stop forced cooling
Confirm that DIP switch SW2 is in COOL mode.
1 Press the forced cooling operation switch SW1 to begin forced cooling.
2 Press the forced cooling operation switch SW1 to stop forced cooling.
SW1
HEAT
COOL
SW2
NOTICE
Take care that while running forced cooling operation, the water temperature
remains higher than 5°C (see temperature read out of the indoor unit). You can
achieve this, for example, by activating all fans of the fan coil units.