Troubleshooting by Indication on the Remote Controller ESIE09-08A
176 Troubleshooting
3.25 “H9 Outdoor Unit: Malfunction of Thermistor (R1T) for
Outdoor Air
Remote Control
Display
H9
Applicable Models ER*Q 011~016*
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed Causes Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PC board (A1P)
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on page 251.
(V3070)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(3.5kΩ to
360kΩ)
Connector
is connected to X11A
of outdoor PC board
(A1P).
Replace outdoor unit PC board
(A1P).
Connect the connector and turn
on again.
NO
NO
Replace the thermistor (R1T).
YES
YES