ESIE09-08A Troubleshooting by Indication on the Remote Controller
Troubleshooting 203
3.52 “PJ” Indoor Unit: Faulty Combination of PCB
Remote Control
Display
PJ
Subcode 11
Applicable Models All indoor units
Method of
Malfunction
Detection
This malfunction is detected according to communications with the inverter.
Malfunction
Decision Conditions
Make judgment according to communication data on whether or not the type of the inverter PCB is
correct.
Supposed Causes Mismatching of type of PCB.
Troubleshooting Caution: Be sure to turn off the power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Replace the inverter PC board assy [A4P (1ø) or A5P (3ø)].