ESIE09-08A Troubleshooting by Indication on the Remote Controller
Troubleshooting 221
[CHECK 3] Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector on motor side disconnected, measure the resistance between each pin,
then make sure that the resistance is more than the value mentioned in the following table.
Measurement point Judgment
1 - 4 1M or more
2 - 4 100k or more
3 - 4 100 or more
4 - 7 100k or more
GND
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red