ESIE09-08A Field Setting
Test Operation 111
[D] Domestic water heating retention times
The heat pump can only work in either space heating operation or domestic water heating operation. No
simultaneous operation is possible, except when using multiple set point control.
[d-00] Set point: minimum operation time for domestic water heating
[d-01] Set point: maximum operation time for domestic water heating
[d-02] Set point: interval minimum stop time of domestic water heating
Changing the timer values can have an impact on space heating and domestic water heating heat up
timers. The default values are proposed but can be changed depending on the complete system
installation.
For a detailed explanation about simultaneous request of space heating and domestic water heating, see
control chapter.
First
code
Second
code Setting name
Default
value Range Step Unit
D Domestic water heating retention times
00 Set point: minimum time for domestic water
heating
10 5~20 1
01 Set point: maximum time for domestic water
heating
30 10~60 5
02 Set point: interval minimum stop time of domestic
water heating
15 5~30 5