EasyManua.ls Logo

Daikin ALTHERMA HT ERSQ 014 V1 - Page 274

Daikin ALTHERMA HT ERSQ 014 V1
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
External Backup Heater Kit ESIE09-08A
264 Appendix
(*): approximate value (depends on operation conditions (e.g. dT, HP indoor unit))
Emergency
operation
(*): approximate value (depends on operation conditions (e.g. dT, HP indoor unit))
Internal starting
conditions
Defrost heat pump
operation
Step 0 -> Step 1
&
Q2L = ON
LWT < ~ LWT setpoint - 15 (*)
LWT < 55°C
Heat request
Step 1 -> Step 2
&
LWT < ~ LWT setpoint - 12 (*)
LWT < 55°C
TM1 up (5 minutes)
Step 2 -> Step 1
or
LWT > ~ LWT setpoint - 6,5 (*)
LWT > 65°C
Step 1 / 2 -> Step 0
&
Q2L = OFF
LWT > 70°C
LWT > ~ LWT setpoint - 3,5 (*)
No heat request
EMERGENCY OPERATION
Step 0
(no BUH operation)
Step 1
Step 2
TM
1
TM
1
Note
The TM* indicate timers, these start counting down if they
are crossed when going from one step over to another
step.
TM1: 5 minutes
Request -> Operation
&
Safe guards not operated
Flow at least 5 seconds at 9l/min
Entering water temperature < 75°C

Table of Contents

Related product manuals