Troubleshooting by Error Code SiUS341802E
181 Service Diagnosis
2.8 Indoor Fan Motor Status Abnormality
Error Code A6-20
Applicable
Models
FXTQ-TA
Outline The indoor unit periodically receives control status information from the fan motor.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the information shows Power Limit or Temp Limit status, it will be deemed a MOTOR LIMIT
abnormal operation. (The system can keep operating.)
If the information shows Motor Lost Control or Current Trip status, it will be deemed a MOTOR
TRIP abnormal operation. (The system stops operating.)
Error Reset
Conditions
If the indoor unit stops receiving abnormal information, the error will be cleared.
Supposed
Causes
îš„ Fan or motor obstruction
îš„ Blocked filters
îš„ Power interruption (low voltage)
îš„ Incorrect wiring
îš„ Blockage in the airflow (ductwork) or ductwork undersized
îš„ High loading conditions
Corrective
Actions
îš„ Check for obstruction on the fan, motor, or ductwork.
îš„ Clean filters.
îš„ Check filters, grille, duct system, heat exchanger air inlet/outlet for blockages.
îš„ Verify the input voltage at the motor.
îš„ Check wiring.
îš„ Replace motor.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Aurora Series and is the answer not in the manual?

Daikin Aurora Series Specifications

General IconGeneral
SeriesAurora
BrandDaikin
Heating Capacity9, 000 - 36, 000 BTU/h (depending on model)
Cooling Capacity9, 000 - 36, 000 BTU/h (depending on model)
Seasonal Energy Efficiency Ratio (SEER)Up to 24.5

Related product manuals