EasyManua.ls Logo

Daikin BRC1E52B7 - Test Operation Method (in the Case of Skyair)

Daikin BRC1E52B7
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BRC1E52B7 Installation manual
4PW72364-1 – 11.2011
16
7. Test operation method (in the case of
SkyAir)
* In the case of VRV, see the manual attached to the outdoor unit.
Also see installation manuals attached to the indoor unit and the outdoor
unit.
Check that wiring work of the indoor unit and the outdoor unit is completed.
Check that switch box cover of the indoor unit and the outdoor unit is closed.
After refrigerant piping, drain piping and electric wiring are completed, clean inside of the indoor unit
and decorative panel.
Perform the test operation according to following procedure.
7-1 Make sure to turn on the power supply
more than 6 hours before operation
start with front panel closed to protect
compressor.
7-2 Conrm that stop valves of both liquid
and gas are opened.
<Make sure that outer panel and
piping cover is closed before
operation (danger of electric
shock). >
* After air purge by vacuum pump,
refrigerant pressure may not rise
even though the stop valve is
opened. The reason is that refriger-
ant system of the outdoor unit is
blocked by electrical expansion valve
or the like. Operation is no problem.
7-3 Set the operation mode to cooling by
using the remote controller.
7-4 Press and hold Cancel button for
4 seconds or longer. Service Settings
menu is displayed.
7-5 Select Test operation in the Service
Settings menu, and press Menu/Enter
button. Basic screen returns and "Test
operation" is displayed.
The backlight will be lit for approximately
30 seconds by pressing any operation button.
Operate the buttons during the backlight lit.
However, On/Off can be operated concur-
rently with the backlight lit.
Notes for backlight
<Basic screen>
7-3
7-4
Cool
Set to
Cool
28°C
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
<Service Setting menu screen>
7-5
Return Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Press Menu/Enter button.

Related product manuals