Specifications Si12-411A
32 Specifications
50Hz 220-230-240V / 60Hz 220-230V
Notes:
1. The data are based on the conditions shown in the table below.
Model 4MKD90BVM
Cooling Capacity
kW
Power Consumption
W
Running Current
A
Casing Color Pale Ivory
Compressor
Type Hermetically Sealed Swing Type
Model 2YC45ZXD
Motor Output W 1,380
Refrigerant Oil
Model SUNISO 4GSD.I.
Charge L 0.75
Refrigerant
Type R22
Charge kg 3.1
Air Flow Rates
/min
H48.5
L42
cfm
H 1,400
L 1,212
Fan
Type Propeller
Motor Output W 51
Running Current A H: 0.44 / L: 0.34
Power Consumption W H: 60 / L: 41
Starting Current A 12.1
Dimensions (H×W×D) mm 908×900×320
Packaged Dimensions (H×W×D) mm 942×926×394
Weight kg 66
Gross Weight kg 77
Operation Sound dBA 48
Piping Connection
Liquid mm
φ
6.4
×
2,
φ
9.5
×
2
Gas mm
φ
12.7
×
1,
φ
15.9
×
3
Drain mm
φ
25.0
Heat Insulation Both Liquid and Gas Pipes
No. of Wiring Connection 3 for Power Supply, 4 for Interunit Wiring
Max. Piping Length
m 70 (for Total of Each Room)
m 25 (for One Room)
Amount of Additional Charge g/m Chargeless
Max. Installation Height Difference
m 15 (between Indoor Unit and Outdoor Unit)
m 7.5 (between Indoor Units)
Drawing No. 3D039670#1
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB
5.0m

Table of Contents

Other manuals for Daikin CDKD35CVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin CDKD35CVM and is the answer not in the manual?

Daikin CDKD35CVM Specifications

General IconGeneral
BrandDaikin
ModelCDKD35CVM
CategoryAir conditioning
LanguageEnglish

Related product manuals