MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO:
1. Solenoid not energized - In order to determine if the
solenoid is energized, touch the nut that holds the solenoid
cover in place with a screwdriver. If the nut magnetically
holds the screwdriver, the solenoid is energized and the
unit is in the cooling cycle.
2. No voltage at units solenoid - Check unit voltage. If no
voltage, check wiring circuit.
3. Valve will not shift:
a. Undercharged - check for leaks;
b. Valve Body Damaged - Replace valve;
c. Unit Properly Charged - If it is on the heating cycle, raise
the discharge pressure by restricting airflow through the
indoor coil. If the valve does not shift, tap it lightly on
both ends with a screwdriver handle. DO NOT TAP THE
VALVE BODY. If the unit is on the cooling cycle, raise the
discharge pressure by restricting airflow through the
outdoor coil. If the valve does not shift after the above
attempts, cut the unit off and wait until the discharge
and suction pressure equalize, and repeat above steps. If
the valve does not shift, replace it.

Other manuals for Daikin DCH072 SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin DCH072 SERIES and is the answer not in the manual?

Daikin DCH072 SERIES Specifications

General IconGeneral
BrandDaikin
ModelDCH072 SERIES
CategoryHeat Pump
LanguageEnglish

Related product manuals