The Digital Controller ESIE11-02
2–30 Part 2 – Functional Description
3
1
2
4
5
REMARK:
Remote cool/heat control can only be used in case p09=9.
Remote on/off control can only be used in case p34=23.
Setting the
temperature
Use the
u and d keys to adjust the water temperature.
When you switch
the unit ON
When you switch the unit ON, the following happens:
Local (h07=0) Remote (h0b=1) Switch remote cool/heat Switch on the unit
automatically.
Only cool/heat selection is
possible.
If start/stop
set-up is...
and cool/heat
set-up is...
, then... to...
Stage Description
1
■ uv2 will appear on the screen, indicating the controller type.
■ 1.9 will appear on the screen, indicating the software version.
2
■ The G symbol or the F symbol lights up, indicating whether the cooling or heating
mode is selected (heating mode only for EUWY*5-24KBZW1).
■ The numeric display shows the actual inlet water temperature.