EasyManua.ls Logo

Daikin EUWAN24KBZW1 - 3.6 Checking the Power Supply and Fuses: EUWA*5-24 KBZW1 and EUWY*5-24 KBZW1

Daikin EUWAN24KBZW1
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Checking the Inputs and Outputs ESIE11-02
3–18 Part 3 – Troubleshooting
3
1
3
4
5
3.6 Checking the Power Supply and Fuses: EUWA*5-24KBZW1 and
EUWY*5-24KBZW1
Overview The table below contains an overview of the circuits, the voltage and their fuse codes.
Circuit Wiring code Type / voltage Fuse code
Main supply L1 + L2 + L3 + N 3 phases / 400 V AC F1+F2+F3
Control circuit I/O PCB L1 + N
L3 + N
1 phase / 230 V AC
1 phase / 230 V AC
F4
F1U
Control circuit controller TR1-sec. 24 V AC F3U, F5U
Control circuit (pump) for
EUWAN5-24KBZW1
X1M 8-7 24 V AC F6
Fan circuit for
EUWA*5-12KBZW1
L1 + N 1 phase / 230 V AC F7
Fan circuit for
EUWA*18-24KBZW1
L1 + N 1 phase / 230 V AC F8

Table of Contents