1.18 Electrical Specifications: EUWY*24KBZW1
Electrical
specifications
The table below contains the electrical specifications.
Model EUWYN24KBZW1 EUWYP24KBZW1 EUWYB24KBZW1
Power supply
Phase 3N~
Frequency 50 Hz
Voltage 400 V
Voltage tolerance ± 10 %
Unit
Starting current 139 A 142 A
Nominal running
current cooling
41.0 A 43.7 A
Max. running
current
53.8 A 56.5 A
Recommended fuses 3 x 63 gL/gG 3 x 63 gL/gG
Fans
Phase 1~
Voltage 230 V
Max. running
current
5.8 A
Compressor
Phase 3~
Voltage 400 V
Starting current 136.0 A
Nom. running
current cooling
17.6 A
Max. running
current
24.0 A
Starting method Direct on line
Control circuit
Phase 1~
Voltage 230 V
Recommended fuses Factory installed
Pump
Phase __ 3~
Voltage __ 400.0 V
Max. running
current
__ 2.7 A