General Outline ESIE11-02
1–44 Part 1 – System Outline
3
11
4
5
Nominal conditions The nominal conditions are as follows:
■ Entering/leaving evaporator water temperature 12.5/7°C
■ Ambient air temperature 35°C
■ Power input is total input: Compressor + control circuit + fans + pump.
Operation range The nominal operation range covers:
■ A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down
condition to 25°C).
■ A leaving condensor water temperature from 35°C to 50°C.