EasyManua.ls Logo

Daikin EUWAN24KBZW1 - 1.13 Electrical Specifications: EUWA*16-20 KBZW1

Daikin EUWAN24KBZW1
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE11-02 General Outline
Part 1 – System Outline 1–35
3
1
4
5
1.13 Electrical Specifications: EUWA*16-20KBZW1
Electrical
specifications
The table below contains the electrical specifications.
Model EUWAN16KBZW1 EUWAP16KBZW1 EUWAB16KBZW1 EUWAN20KBZW1 EUWAP20KBZW1 EUWAB20KBZW1
Power supply
Phase 3N~
Frequency 50 Hz
Voltage 400 V
Voltage tolerance ± 10 %
Unit
Starting current 97.9 A 99.9 A 113 A 115 A
Nominal running
current
27.2 A 29.2 A 31.8 A 33.8 A
Max. running
current
33.8 A 35.8 A 39.8 A 41.8 A
Recommended
fuses
3 x 40 gL/gG 3 x 50 gL/gG 3 x 50 gL/gG 3 x 50 gL/gG
Fans
Phase 1~
Voltage 230 V
Max. running
current
5.8 A
Compressor
Phase 3~
Voltage 400 V
Starting current 95.0 A 110.0 A
Nom. running
current
10.7 A 13.0 A
Max. running
current
14.0 A 17.0 A
Starting method Direct on line
Control circuit
Phase 1~
Voltage 230/ 24 V AC (supplied by factory installed transformers)
Recommended
fuses
Factory installed
Crankcase heater
(E1/2 HC)
50 W
Pump
Phase __ 3~ __ 3~
Voltage __ 400.0 V __ 400.0 V
Max. running
current
__ 2.0 A __ 2.0 A

Table of Contents