ESIE11-02 The Digital Controller
Part 2 – Functional Description 2–35
3
2
4
5
1
Consulting actual
operational
information
The actual operational information that can be consulted in the list of direct parameters consists of:
b01: Evaporator inlet water temperature,
b02: Evaporator outlet water temperature,
b03: Not used,
c10: Total running hours of the compressor 1,
c11: Total running hours of the compressor 2,
c15: Total running hours of the pump.
REMARKS:
The parameters b01, b02 and b03 can also be consulted by the "sensor readout menu". Refer
to "How to consult and modify the ‘sensor readout menu’ parameters" on page 2–34.
To reset the timers of parameters c10, c11 and c15 refer to "Resetting warnings" on page 3–10.
These are direct parameters, refer to "How to consult and modify the direct parameters" on page 2–33.