General Outline ESIE11-02
1–6 Part 1 – System Outline
3
11
4
5
(1)
: The table below contains the minimum water volume settings.
(2)
: The sound power level is an absolute value that does not depend on the surroundings or the
distance. It cannot be measured in the field (ISO 9614).
No. of circuits 1
Pump
No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction
Model __ CM3-3 CM3-3
Nominal static
height pump
__ 239 kPa 198 kPa
Nominal static
height unit
__ 209 kPa 128 kPa
Hydraulic components
Buffer tank __ 55 l __ 55 l
Unit water volume 2l 3l 59l 3l 3l 59l
Expansion vessel __ 12 l __ 12 l
Pre-pressure
expansion vessel
1.5 bar 1.5 bar
Safety valve __ 3 bar __ 3 bar
Dimensions
(h x w x d)
1230 x 1290 x 734 mm 1230 x 1290 x 734 mm
Weight
Machine weight 150 kg 168 kg 180 kg 215 kg 229 kg 241 kg
Operation weight 152 kg 171 kg 239 kg 218 kg 232 kg 300 kg
Casing
Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material Polyester coated galvanised steel plate
Sound power
level
(2)
67 dBA 76 dBA
Safety devices
Low-pressure switch
High-pressure switch
Pump motor overcurrent
Discharge temperature control
Outlet water temperature protection
Compressor motor overcurrent relay
Fan thermal protector
Anti-recycling and guard timer
Digital display controller with electronic temperature control
Reverse phase protector
Flow switch.
Model EUWAN5KBZW1 EUWAP5KBZW1 EUWAB5KBZW1 EUWAN8KBZW1 EUWAP8KBZW1 EUWAB8KBZW1
Setting EUWA*5-8KBZW1
The minimum water volume for standard thermostat difference setting 3 K
For reduced setting multiply this water volume by 3/new setting
Minimum allowable setting 0.1 K

Table of Contents