General Outline ESIE11-02
1–24 Part 1 – System Outline
3
11
4
5
(1)
: The table below contains the minimum water volume settings.
Oil charge volume 2 x 2.7 l
No. of circuits 2
Pump
No. x type __ 1 x Horizontal multi-stage end-suction __ 1 x Horizontal multi-stage end-suction
Model __ CM10-2 __ CM10-2
Nominal static
height pump
__ 302 kPa __ 296 kPa
Nominal static
height unit
__ 249 kPa __ 229 kPa
Hydraulic components
Buffer tank __ 55 l __ 55 l
Unit water volume 6l 9l 65l 6l 10l 66l
Expansion vessel __ 12 l __ 12 l
Pre-pressure
expansion vessel
1.5 bar
Safety valve __ 3 bar __ 3 bar
Dimensions
(h x w x d)
1321 x 2580 x 734 mm 1541 x 2580 x 734 mm
Weight
Machine weight 455 kg 473 kg 485 kg 516 kg 534 kg 546 kg
Operation weight 461 kg 482 kg 550 kg 522 kg 544 kg 612 kg
Casing
Colour Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material Polyester coated galvanised steel plate
Sound power
level
(2)
79 dBA 81 dBA
Safety devices
Low-pressure switch
High-pressure switch
Pump motor overcurrent
Discharge temperature protection
Outlet water temperature protection
Compressor motor overcurrent relay
Fan thermal protector
Anti-recycling and guard timer
Digital display controller with electronic temperature control
Reverse phase protector
Flow switch.
Model EUWYN16KBZW1 EUWYP16KBZW1 EUWYB16KBZW1 EUWYN20KBZW1 EUWYP20KBZW1 EUWYB20KBZW1
Setting EUWY*16-20KBZW1
The minimum water volume for standard thermostat difference setting 3 K
For reduced setting multiply this water volume by 3/new setting
Minimum allowable setting 0.1 K