ESIE11-05 Remote Controller
Functional Description 91
8.2.2 [1] Settings Are Not Applicable
Not applicable.
8.2.3 [2] Automatic Setback Function
Setback function provides the possibility to lower the room temperature/water temperature. The
setback function can for instance be activated during the night because the temperature
demands during night and day are not the same.
[2-00] Status: defines whether the setback function is turned ON (1) or OFF (0)
[2-01] Start time: time at which setback is started
[2-02] Stop time: time at which setback is stopped
Setback can be configured for both room temperature control and leaving water temperature
control.
Refer to “[5] Automatic Setback” on page 92 for temperature set points.
NOTE
By default the setback function is enabled.
The setback function can be combined with the automatic weather dependent
set point operation.
Setback function is an automatic daily scheduled function.
A Normal room temperature set point
B Room setback temperature
t Time
T Temperature
A Normal leaving water temperature set point
B Leaving water setback temperature
t Time
T Temperature
NOTE
Setback function for cooling does not exist.
[2-01] [2-02]
A
T
t
21°C
B [5-03] 18°C
[2-01] [2-02]
B
A
T
t
45°C
40°C
5°C [5-02]