84 Functional Description
8.2 Field Setting
Field setting from
remote control
Individual function of hydrobox can be changed from the remote control. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the hydrobox, setting for the hydrobox may be
required to change. Refer to information in the option handbook.)
Wired remote
control
EKRUAHTB
(BRC21A52)
To change one or more field settings, proceed as follows.
1. Press the z button for a minimum of 5 seconds to enter FIELD SET MODE.
The $ icon (c) will be displayed. The current selected field setting code is indicated
; (b), with the set value displayed to the right - (a).
2. Press the Lbi button to select the appropriate field setting first code (8-).
3. Press the Lbj button to select the appropriate field setting second code (-88).
4. Press the pfi button and pfj button to change the set value of the select field
setting.
5. Save the new value by pressing the pr button.
6. Repeat step 2 through 4 to change other field settings as required.
7. When finished, press the z button to exit FIELD SET MODE
.