List of Electrical and Functional Parts ESIE11-05
182 Service Procedure
1. List of Electrical and Functional Parts
1.1 EW*Q016BA
Item Name Symbol
Compressor
Inverter
Type
M1C
JT1GCVDKYR@T
OC protection
device
14.7A
STD 1
Type
M2C
OC protection
device
STD 2
Type
M3C
OC protection
device
Fan motor
OC protection
device
M1F 1.15A 3A
Electronic expansion valve coil (Main) Y1E Fully closed: 0pls Fully open: 480pls
Electronic expansion valve coil (Subcooling) Y2E
Fully closed: 0pls
Fully open: 480pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH
For M3C S3PH
Low pressure sensor S1NPL OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 93°C
Others Fuse
For main PCB
A1P 250V, 15A
A2P 250V, 3A
For Noise filter
PCB
F1U 250V AC 5A Class B