Remote Controller ESIE11-05
96 Functional Description
8.2.15 [E] Service Mode
[E-01] Setting not available.
[E-02] Setting not available.
[E-03] Setting not available.
[E-04] Pump only operation
When commissioning and installing the unit it is very important to get all air out of the water
circuit.
Through this field setting the pump can be operated without actual operation of the unit. By
doing so this will enhance the air removal from the circuit. The pump can operate at different
speed:
[E-04]=0 normal operation of the unit (default)
[E-04]=1 program 1
[E-04]=2 program 2
8.2.16 [F] Settings Are Not Applicable
Not applicable.
[E-04]=1 program 1 the unit will
perform the automatic air purge
operation for 108 minutes.
[E-04]=2 program 2 the unit will perform
the automatic air purge operation for 48
minutes.
[E-04]=1
Pump operation for 10 minutes
108 minutes
Pump stops operation for 2 minutes
[E-04]=2
Pump operation for 10 minutes
48 minutes
Pump stops operation for 2 minutes