ESIE11-05 Field Setting from Outdoor Unit
Functional Description 73
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory setting
0
Digital pressure
gauge kit display
khhhhhh
Address 0
khhhhhh
Binary number 1
khhhhhk
(4 digits)
~
15
khhkkkk
2
Low noise/demand
address
khhhhkh
Address 0
khhhhhh
Binary number 1
khhhhhk
(6 digits) ~
31
khkkkkk
12
External low noise/
demand setting
khhkkhh
External low noise/demand:
NO
khhhhhk
External low noise/demand:
YES
khhhhkh
18
High static pressure
setting
khkhhkh
High static pressure setting:
OFF
khhhhhk
High static pressure setting:
ON
khhhhkh
19
Emergency
operation
(STD compressor is
inhibited to operate.)
khkhhkk
OFF
khhhhhh
STD 1, 2 operation: Inhibited
khhhhhk
STD 2 operation: Inhibited
khhhhkh
20
Additional refrigerant
charging operation
setting
khkhkhh
Refrigerant charging: OFF
khhhhhk
Refrigerant charging: ON
khhhhkh
21
Refrigerant
recovery/vacuuming
mode setting
khkhkhk
Refrigerant recovery / vacuuming: OFF
khhhhhk
Refrigerant recovery / vacuuming: ON
khhhhkh
22
Night-time low noise
setting
khkhkkh
OFF
khhhhhh
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhhkk
25 Low noise setting
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start
setting
khkkhkh
About 20:00
khhhhhk
About 22:00 (factory setting)
khhhhkh
About 24:00
khhhkhh
27
Night-time low noise
operation end
setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00 (factory setting)
khhhkhh
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk
ON
khhhhkh
29
Capacity priority
setting
khkkkhk
OFF
khhhhhk
ON
khhhhkh
30 Demand setting 1
khkkkkh
60% demand
khhhhhk
70% demand
khhhhkh
80% demand
khhhkhh
32
Normal demand
setting
kkhhhhh
OFF
khhhhhk
ON
khhhhkh
38
Emergency
operation
kkhhkkh
OFF
khhhhhk
Master unit operation: Inhibited
khhhhkh