Daikin FCQ18PVJU - J3 Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R2 T)

Daikin FCQ18PVJU
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiUS28-902_a Troubleshooting by Indication on the Remote Controller
Troubleshooting 114
3.23 J3” Outdoor Unit: Malfunction of Discharge Pipe
Thermistor (R2T)
Remote
Controller
Display
J3
Applicable
Models
RZQ18~30PVJU
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R2T) for outdoor unit discharge pipe
Defect of outdoor unit P.C.B. (A1P)
Troubleshooting
Refer to Thermistor Resistance / Temperature Characteristics table on P.167.
Caution
Be sure to turn off the power switch before connecting or disconnecting
the connector, or parts could be damaged.
Resistance
is normal when
measured after
disconnecting the thermistor
R2T from the outdoor
unit P.C.B.
(5.0kΩ~
640kΩ)
Replace the outdoor unit P.C.B.
(A1P).
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R2T).
YES
YES
Connector
is connected to
outdoor unit
P. C . B .
(A1P).