SiUS28-902_a Special Control
Function 28
3.7 Pressure Equalization Prior to Startup
Before activating the compressor, the activation load is lightened by equalization across the
compressor. In addition, inverters turn on electricity and capacitors are charged.
Actuator Operation Remarks
Compressor OFF
Outdoor unit fan
Cooling:OFF
Heating:Ta>78.8°F; STEP 8,
Ta78.8°F; OFF
Four-way valve Keep former condition.
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV2)
0 pls
Hot gas bypass valve (SVP) ON
Receiver gas discharging valve (SVG) OFF
Ending conditions
3 min.
Pc-Pe<29 psi
or